HJJES Series – The Guide HazLoc Exit Sign

CERTIFICATIONS / RATINGS

UL STANDARDS
• UL844 | UL 924

NEC and CEC
• Class I, Div 1 – Groups B, C, D
• Class I, Div 2 – Groups A, B, C, D
• Class II, Div 1 – Groups E, F, G
• Class II, Div 2 – Groups F, G
• Class III

• UL Listed
• IP66
• CSA C22.2 No. 137-18
• UL 121201 / CSA No. 213
• See Specification Sheet For Complete Listing

KEY FEATURES AND BENEFITS

• 180 minute battery backup.
• High vibration / anti-resonance design.
• Ambient temperature capabilities -10˚C (14˚F) to 60˚C (140˚F).
• Corrosion proof – coated aluminum alloy (copper free) housing.
• Low wattage requirements of 3w and 5w..
• Paint/spray listed for use in paint or powder booths.
• Suitable for wet locations.
• Double or single sided exit sign.
• One-piece silicone gasket.
• Stanless steel hardware and mounting sling

DOWNLOADS

 

 

 

SPECIFICATIONS

Voltage 100-277vAC
Wattage 3w / 5w
Housing A356T6 aluminum with baked-on gray epoxy finish
Color Gray with red letters
Sign Plate Tempered glass
Lifetime 50,000 hrs L70
Ambient Temperature -10°C (14°F) to 60°C (140°F)
Power Factor > 0.98
NPT 3/4”
Warranty 5 Year Limited Warranty

See specification sheet for product ordering selection, mounting options, weights and dimensions.